Back Button EDS11-167A Datasheet HTML 3Page - Fuji Electric EDS11-167A Datasheet HTML 4Page - Fuji Electric EDS11-167A Datasheet HTML 5Page - Fuji Electric EDS11-167A Datasheet HTML 6Page - Fuji Electric EDS11-167A Datasheet HTML 7Page - Fuji Electric EDS11-167A Datasheet HTML 8Page - Fuji Electric EDS11-167A Datasheet HTML 9Page - Fuji Electric EDS11-167A Datasheet HTML 10Page - Fuji Electric EDS11-167A Datasheet HTML 11Page - Fuji Electric Next Button
Zoom Inzoom in Zoom Outzoom out
 7 / 12 page
background image
7
Operation parameter
Parameter (name)
Read/write date setting range
Factory default
Registor No.
Run/Standby switch
0: Run
1: Standby
0 (RUN)
40021
Digital input latch releases command
0: OFF
1: Release latch
0 (OFF)
40022
Digital output latch releases
command
0: OFF
1: Release latch
0 (OFF)
40023
Communication parameter
Parameter (name)
Read/write date setting range
Factory default
Registor No.
RS-485 Parity setting
0: NONE
1: ODD
2: EVEN
0 (NONE)
40111
RS-485 Response interval time
0 to 25 (×20ms)
1
40113
RS-485 Communication permission
0: Read only
1: Read/Write
1 (R/W)
40114
RS-485 Communication speed
0: 9.6kbps
1: 19.2kbps
2: 38.4kbps
3: Forbidden
4: 115.2kbps
1 (9.6kbps)
40115
Enhanced communication module
(PUMC) connection
0: PUMC not connected (RS485 Enable)
1: PUMC connected (RS485 Disable)
040116
Configuration parameter
Parameter (name)
Read/write date setting range
Factory default
Registor No.
FAULT output set value
0: HOLD
1: OFF
0 (HOLD)
40260
Standby output set value
0000 to FFFF
0000
40268
Standby mode setting
0: DI=Input value, DO=Standby output set value
1: DI=All OFF, DO=Standby output set value
0
40270
LED2 Lamp Allocation
0 to 2
1
40222


Html Pages

1  2  3  4  5  6  7  8  9  10  11  12 


Datasheet Download

Go To PDF Page


Link URL




Privacy Policy
ALLDATASHEET.COM
Does ALLDATASHEET help your business so far?  [ DONATE ]  

About Alldatasheet   |   Advertisement   |   Datasheet Upload   |   Contact us   |   Privacy Policy   |   Alldatasheet API   |   Link Exchange   |   Manufacturer List
All Rights Reserved© Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn