background image
2
www.power-one.com
Edition 5/07.2001
Input
Input voltage
world wide mains, single phase
85...264 V AC
derating information see application note
90...350 V DC
Input frequency
14...440 Hz
Power factor
active PFC
up to 0.99
Inrush current
virtually no inrush current
Output
Efficiency
Ui nom, Io nom
up to 89%
Output voltage setting accuracy
Ui nom, Io nom
± 1.3% U
o nom
Output voltage noise
IEC/EN 61204
typ. 50 mV
Output voltage ripple
sinusoidal output ripple at wice the line frequency
≤1.2 V
pp
Line and cross regulation
Ui min...Ui max
typ. 50 mV
Load regulation
0...100%
Io nom, Ui nom
–1.6%
Uo nom
Minimum load
not required
Current limitation
rectangular U/I characteristic
101...112%
Io nom
Short term peak power
1 s, electronically controlled
150 %
Io nom
Operation in parallel
enabled by droop current share
Hold-up time
Io nom, Uo decreases to 80% of Uo nom
typ. 15 ms
Control
Status indication
LED output(s) OK
Protection
Input fuse
not user accessible 6.3 A, slow blow
Input reverse polarity
bridge rectifier
Input undervoltage lockout
typ. 80 %
Ui min
Input overvoltage lockout
typ. 105%
Ui max
Input transient protection
voltage depending resistor (VDR)
Output(s)
no-load, overload and short circuit proof
Output overvoltage
second control loop, each output, 24 V/48 V
30/60 V SELV
Overtemperature
reduced output power if thermally overloaded
Safety
Approvals
EN 60950, UL 1950, CSA22.2 No. 950, UL 508 listed
Electric strength test voltage
class I, I/case
2 kV AC
class I, I/O
3 kV AC
class I, O/case
1 kV AC
class I, O/O
0.35 kV AC
Pollution degree
AC-in / DC-in
3/2
Degree of protection
IP 20
W Series
125 and 250 Watt AC-DC Converters


Html Pages

1  2  3  4  5 


Datasheet Download

Go To PDF Page


Link URL




Privacy Policy
ALLDATASHEET.COM
Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Datasheet Upload   |   Contact us   |   Privacy Policy   |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn