1 / 2 page
Specifications are subject to change without notice
1
• For AC current/voltage measurement
• Field adjustment capability
• For DIN-rail mounting
• Degree of protection: IP 50
Product Description
Model
Range code
Measurement
Power supply
Setpoints
Rated output
Calibration
Ordering Key
CVT-DIN AV5AD01X
Compact transducer for AC
current/voltage measurements
with field adjustment capabil-
ity. The housing is for DIN-rail
mounting
and
ensures
a
degree of protection of IP 50.
Energy Management
Compact Transducer for AC Measurements
Type CVT-DIN AV1/AV4/AV5
Type Selection
Power supply
A:
24 VAC, -15% +10%,
50/60 Hz 1)
B:
48 VAC, -15% +10%,
50/60 Hz 1)
C:
115 VAC, -15% +10%,
50/60 Hz 1)
D:
230 VAC, -15% +10%,
50/60 Hz (standard)
1) On request
Range code
AV1:
100 VAC - 1 AAC
(max. 120 VAC - 1.2 A)
AV4:
100 VAC - 5 AAC
(max. 120 VAC - 6 A)
AV5:
500 VAC - 5 AAC
(max.600 VAC - 6 A)
Rated output
1:
Analogue output
0 to 20 mA (standard)
2:
Analogue output
4 to 20 mADC 1)
3:
Analogue output
0 to 10 VDC 1)
4:
Analogue output
0 to ±1 VDC 1)
Calibration
X:
Standard calibration
Y:
Special calibration,
use ”Y” followed by
requested value
Input Specifications
Accuracy
(@ 25°C ± 5°C, R.H.
≤ 60%)
± 0.5% f.s.,
(0.1 ln/Un to 1 In/Un)
Additional errors:
The given accuracy already
includes: frequency, power
supply, output load influences
Humidity
< 0.3%, 60% to 90% R.H.
Input frequency
< 0.4%, 62 to 400 Hz
Magnetic field
< 0.5%, @ 400 A/m
Ripple
≤ 1% according to IEC
60688-1 and EN 60688-1
Rated input
AV1:
1 A (1 V internal shunt/1
Ω imp)/
100 VAC (200 k
Ω impedance)
AV4:
5 A (250 mV internal shunt/
0,05
Ω impedance) /
100 VAC (200 k
Ω imp.)
AV5:
5 A (250 mV internal shunt/
0,05
Ω impedance) /
500 VAC (1 M
Ω imp.)
AC frequency range
48 to 62 Hz
Overload protection
Cont.:
Current:
1.2 x rated input
Voltage:
1.2 x rated input
For 1 s: Current:
20 x rated input
Voltage:
2 x rated input