5 / 13 page
Specifications are subject to change without notice
CPT-DINADS110706
5
CPT-DIN
• RS485/RS422/RS232 communication port
• Analogue outputs (“max” variables, “energies” and “hour counter” excluded)
• Alarm outputs (“max” variables, energies and “hour counter” excluded)
• Pulse outputs (only “energies”)
• Dupline bus (only “total energies” + up to 8 selectable variables)
No
Variable
1-phase
2-phase
3-ph. 4-wire 3-ph. 4-wire 3-ph. 3-wire
3-ph. 3-wire
Notes
system
system
balanced sys. unbal. sys.
bal. sys.
unbal. sys.
1
V L1
x
x
x
x
o
o
2
V L2
o
x
x
x
o
o
3
V L3
o
o
x
x
o
o
4
V L-N sys
o
x
x
x
o
o
Sys = system
5
V L1-2
o
x
x
x
x
x
6
V L2-3
o
x
x
x
x
x
7
V L3-1
o
o
x
x
x
x
8
V L-L sys
o
x
x
x
x
x
Sys = system
9
A L1
x
x
x
x
x
x
#
10
A L2
o
x
x
x
x
x
#
11
A L3
o
o
x
x
x
x
#
12
Amax/
x
x
x
x
x
x
xHighest value
Admd max
among the 3-ph
13
An
o
x
x
x
x
x
14
W L1
x
x
x
x
o
o
x
15
W L2
o
x
x
x
o
o
x
16
W L3
o
o
x
x
o
o
x
17
W sys
o
x
x
x
x
x
Sys = system
18
var L1
x
x
x
x
o
o
19
var L2
o
x
x
x
o
o
20
var L3
o
o
x
x
o
o
21
var sys
o
x
x
x
x
x
Sys = system
22
VA L1
x
x
x
x
o
o
23
VA L2
o
x
xx
o
o
24
VA L3
o
o
x
x
o
o
25
VA sys
o
x
x
x
x
x
Sys = system
26
PF L1
x
x
x
x
o
o
#
27
PF L2
o
x
x
x
o
o
#
28
PF L3
o
ox
x
o
o
#
29
PF sys
o
x
x
x
x
x
Sys = system
30
Hz
x
x
x
x
x
x
31
Phase seq.
o
o
x
x
x
x
32
ASY L-N
o
x
x
xx
x
33
ASY L-L
o
x
x
x
x
x
34
VA sys dmd
x
x
x
x
x
x
Sys = system x
35
W sys dmd
x
x
x
x
x
x
Sys = system x
36
A L1 dmd
x
x
x
x
x
x
dmd = ( * )
37
A L2 dmd
o
x
x
x
x
x
dmd = ( * )
38
A L3 dmd
o
o
x
x
x
x
dmd = ( * )
39
VA L1 dmd
x
x
x
x
x
x
dmd = ( * )
40
VA L2 dmd
o
x
x
x
x
x
dmd = ( * )
41
VA L3 dmd
o
o
x
x
x
x
dmd = ( * )
42
W L1 dmd
x
x
x
x
x
x
# dmd = ( * )
43
W L2 dmd
o
x
x
x
x
x
# dmd = ( * )
44
W L3 dmd
o
o
x
x
x
x
# dmd = ( * )
45
kWh
x
x
x
x
x
x
Total and partial
46
kvarh
x
x
x
x
x
x
Total and partial
47
hours
x
x
x
x
x
x
(x) = available
(o) = not available
(x) These variables are available also for the MAX values stored in the EEPROM when the instrument switches off.
(
#) These variables are available also for the MIN values stored in the EEPROM when the instrument switches off.
( * ) dmd value integrated in a programmed time interval.
(#) The variables are available also for the max values. When the instrument switches off, the values are not stored.
List of the variables that can be connected to: