LC1K1201E7 Datasheet(PDF) 2 Page - Schneider Electric

Part No. LC1K1201E7
Description  TeSys K contactor - 3P - AC-3 <= 440 V 12 A - 1 NC aux. - 48 V AC coil
Download  3 Pages
Scroll/Zoom Zoom In 100%  Zoom Out
Manufacturer  SCHNEIDER [Schneider Electric]
Direct Link  https://www.se.com/us/en/
Logo SCHNEIDER - Schneider Electric

LC1K1201E7 Datasheet(HTML) 2 Page - Schneider Electric

  LC1K1201E7 Datasheet HTML 1Page - Schneider Electric LC1K1201E7 Datasheet HTML 2Page - Schneider Electric LC1K1201E7 Datasheet HTML 3Page - Schneider Electric  
Zoom Inzoom in Zoom Outzoom out
 2 / 3 page
background image
[Ith] conventional free air thermal
current
20 A 122 °F (50 °C) power circuit
10 A 122 °F (50 °C) signalling circuit
Irms rated making capacity
110 A AC signalling circuit IEC 60947
144 A AC power circuit NF C 63-110
144 A AC power circuit IEC 60947
Rated breaking capacity
110 A 440 V IEC 60947
80 A 500 V IEC 60947
70 A 660...690 V IEC 60947
Associated fuse rating
25 A gG <= 440 V power circuit
25 A aM power circuit
10 A gG signalling circuit IEC 60947
10 A gG signalling circuit VDE 0660
Average impedance
3 mOhm - Ith 20 A 50 Hz power circuit
Insulation resistance
> 10 MOhm signalling circuit
Inrush power in VA
30 VA 68 °F (20 °C))
Hold-in power consumption in VA
4.5 VA 68 °F (20 °C))
Heat dissipation
1.3 W
Control circuit voltage limits
Operational: 0.8...1.15 Uc (at <50 °C)
Drop-out: 0.2...0.75 Uc (at <50 °C)
Maximum operating rate
3600 cyc/h
Auxiliary contacts type
type instantaneous 1 NC
Signalling circuit frequency
<= 400 Hz
Minimum switching current
5 mA signalling circuit
Minimum switching voltage
17 V signalling circuit
Operating time
10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Non overlap distance
0.02 in (0.5 mm)
Mechanical robustness
Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Environment
Product certifications
CSA
UL
Protective treatment
TC conforming to IEC 60068
TC conforming to DIN 50016
Operating altitude
2000 m without derating
Flame retardance
V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
Ordering and shipping details
Category
22326 - CTR,K-LINE,AC,OPEN,NONREV
Discount Schedule
I12
GTIN
03389110858808
Nbr. of units in pkg.
1
Package weight(Lbs)
0.4 lb(US) (0.18 kg)
Returnability
No
Country of origin
FR
2


Html Pages

1  2  3 


Datasheet Download

Go To PDF Page


Link URL




Privacy Policy
ALLDATASHEET.COM
Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Datasheet Upload   |   Contact us   |   Privacy Policy   |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn