2 / 3 page
Du line®
Fieldbus
Installationbus
2
Specifications are subject to change without notice (28.09.99)
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
FK3C3, FK4C3
F.3C 3508 ...
F.3C 3616 ...
F.4C 3732 ...
( 8 channels)
(16 channels)
(32 channels)
Output
1 NPN transistor
1 NPN transistor
1 NPN transistor
Output voltage range VBB
4 to 35 VDC (or VDD in)
4 to 35 VDC (or VDD in)
4 to 35 VDC (or VDD in)
Reverse-polarity protection
Yes
Yes
Yes
Current per output
≤ 100 mA
≤ 100 mA
≤ 100 mA
Short-circuit protection
None
None
None
Built-in protective diodes
None
None
None
Off-state leakage current
≤ 100 µA
≤ 100 µA
≤ 100 µA
Output voltage drop
≤ 1.5 V
≤ 1.5 V
≤ 1.5 V
Cable length
≤ 3 m
≤ 3 m
≤ 3 m
Dielectric voltage
Output - Dupline®
None
None
None
Output connection
2.8 mm faston
2.8 mm faston
2.8 mm faston
Dupline® connection
2.8 mm faston
2.8 mm faston
2.8 mm faston
Response time
< 2 pulse trains
< 2 pulse trains
< 2 pulse trains
Display/Output Specifications (cont.)
Supply Specifications
General Specifications
Power supply AC types
Overvoltage cat. III (IEC 60664)
Operational voltage
through pins A1 & A2 220
230 VAC +6%, -15% (IEC 60038)
120
120 VAC ± 10% (IEC60038)
024
24 VAC ± 10%
Frequency
45 to 65 Hz
Voltage interruption
≤ 40 ms
Rated operational power
Typ. 6 VA
Rated impulse withstand
voltage
220
4 kV
120
2.5 kV
024
800 V
Dielectric voltage
Supply - Dupline®
≥ 2 kVAC (rms)
Supply - Output
≥ 2 kVAC (rms)
Alternative DC supply
Overvoltage cat. III (IEC 60664)
Operational voltage (VDD in)
through pins 2 & 3
FK...
12 VDC ± 10%
(ripple included)
Reverse polarity protection
Yes
Rated operational current
FK3C 3508
≤ 125 mA
FK3C 3616
≤ 250 mA
FK4C 3732
≤ 500 mA
Inrush current
≤ 1 A
Transient protection voltage
800 V
Dielectric voltage
Supply - Dupline®
None
Supply - Output
None
Supply connection
2.8 mm faston
Output-off delay
upon loss of Dupline® carrier
≤ 3 s, (LCD irregular
display indication)
Power ON delay
Undefined
≤ 1 s
Indication for
Loss of Dupline® carrier
LED, red
Environment
Degree of protection
IP 40
Pollution degree
3 (IEC 60664)
Operating temperature
0° to +50°C (+32° to +122°F)
Storage temperature
-20° to +60°C (-4° to +140°F)
Humidity (non-condensing)
20 to 80%
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
Material
(see "Technical Information")
F.3C: 96 x 48 - Housing
F.4C: 144 x 48 - Housing
Weight
F.3C 3508
300 g
F.3C 3616
300 g
F.4C 3732
400 g
Approvals
CSA, UL