1 / 4 page
Specifications are subject to change without notice
EM10DINDS270906
1
• Class 1 (kWh) according to EN62053-21
• Energy meter
• Energy: 5+1 DGT
• Energy measurements: total kWh
• TRMS measurements of distorted sine waves (volt-
ages/currents)
• Self power supply
• Dimensions: 1-DIN module
• Protection degree (front): IP40
• 1 pulse output on request
• MID “annex MI-003” (Measuring Instruments Directive)
compliant
Product Description
One-phase
energy
meter
with LCD data displaying;
indicated for active energy
metering. Housing for DIN-
rail mounting, IP40 (front)
protection
degree.
Direct
Energy Management
Energy Meter
Type EM10 DIN
connection
up
to
32A.
Moreover the meter can be
provided with pulse output
proportional to the active
energy being measured.
Model
Range code
System
Power supply
Output
Option
How to order EM10 DIN AV8 1 X O1 X
Type Selection
Range code
AV7:
120VLN AC - 5(32)A (**)
(direct connection)
AV8:
230VLN AC - 5(32)A (*)
(direct connection)
Option
X:
None (*)
P:
PTB approval
System
1:
1-phase
Output
XX:
None (*)
O1:
Pulse type (open col-
lector output) (*)
Power supply
X:
Self power supply
(from 48 to 62Hz).
The instrument
works on the range
from -20% to +20%
of the measuring
nominal input
voltage.
(*) as standard.
(**) on request.
Rated inputs
System: 1
Current range (by shunt)
AV7 and AV8: 5(32)A
Voltage range
AV7: 120 VLN AC
AV8: 230 VLL AC
Accuracy (Display)
(@25°C ±5°C, R.H.
≤60%,48to62Hz)
AV7 model
Ib: 5A, Imax: 32A;
Un: 120VLN (-20% +20%)
AV8 model
Ib: 5A, Imax: 32A;
Un: 230VLN (-20% +20%)
Active energy
Class 1 according to
EN62053-21 and MID
Annex MI-003 Class B.
Reference values
Ib: 5A, Imax: 32A,
0.1 Ib: 0.5A
Start up current:
20mA
Energy additional errors
Influence quantities
According to EN62053-21,
EN62053-23
Temperature drift
≤200ppm/°C
Sampling rate
1600 samples/s @ 50Hz
1900 samples/s @ 60Hz
Display
1 line (max: 5+1 DGT)
Type
LCD, h 7mm
Energie indication
Total: 5+1 DGT
LEDs
Red LED (Energy con-
sumption), 1000 pulses/kWh
(Max Frequency 16 Hz)
according to EN62053-11
Measurements
kWh from 0,0 to 99999,9
Method
TRMS measurements of
distorted wave forms
Coupling type
Direct
Crest factor
Ib 5A
≤4 (45A max. peak)
Current Overload
Continuous
32A, @ 50Hz
For 10ms
960A, @ 50Hz
Voltage Overload
Continuous
1.2 Un
For 500ms
2 Un
Input impedance
120VL-N (AV7)
>720K
Ω
230VL-N (AV8)
>720K
Ω
5(32) A (AV7-AV8)
< 0.5VA
Frequency
48 to 62 Hz
Input specifications