10 / 14 page E5AX-P E5AX-P 10 Lower/Upper Limits of Setting Range: sl–l, sl–h –200 0 400 1,300 SL-L SL-H Basically, the temperature range that can be measured is deter- mined by the temperature sensor to be used. For example, when a K-type (chromel-alumel thermocouple) temperature sensor is se- lected, the measurable range is from –200%C to 1,300%C. Howev- er, this temperature range can be narrowed, for example, to 0%C to 400%C. To do this, set the lower-limit value of the temperature set- ting range, in this case to 0%C, on the SV display by using the Up and Down Keys while 5l–l is displayed on the PV display. Similarly, set the upper-limit value, 400%C, while 5l–h is displayed. If the pro- cess temperature falls below the set lower-limit value or exceeds the set upper-limit value, it is displayed on the PV display within the temperature range of the temperature sensor. Hysteresis Alarm: hysa The hysteresis alarm value for the alarm can be set in a range from 0.0% to 999.9%C while hysa is displayed on the PV display using the Up and Down Keys. The factory setting is 0.2%C/%F. Disable band: db The disable band can be set in a range from 0.1% to 10.0% while db is displayed on the PV display using Up and Down Keys. The factory setting is 2.0%. Motor Calibration: calb Designate whether or not to perform motor calibration. To enter the mode, simultaneously press the Up and Down Keys for at least one second. Press the Display Key to return to sl–l. WARNING Never calibrate the motor during control operation. Make sure that control operations have been stopped before calibrating. fr–h Fully open position fr–l Fully closed position mot Opening/closing time The motor is calibrated. Refer to page 9. Level 2 In level 2, selected input sensor, and modes for alarm output can be monitored. Note that level 2 is a monitoring level only and thus no parameters can be changed. When the Level Key is pressed for 2 seconds minimum after power application, 5l–l is displayed on the PV display. Hold down the Level Key again for 2 seconds minimum to display o on the PV display. Then, selected input sensor, and alarm modes can be monitored each time the Display Key is pressed. in–t al k ca Press a. Alarm mode Input type Press a. –––( Input Type: in–t When in–t is displayed on the PV display, the present setting of the input type selector (SW206), is displayed on the SV display. The fol- lowing table shows the messages that may be displayed: Display Sensor r pr R 5 pr S k ca K j ic J t cc T e cr E jpt JPt100* pt Pt100** l ic L u cc U *Meets JIS 1981. **Meets JIS 1989, DIN. AL (Alarm Mode): al When al is displayed on the PV display in level 2, alarm output mode or the present setting of the corresponding alarm mode selector (SW205) is displayed on the SV display. The following table shows the messages that may be displayed. Display Alarm mode No display No alarm )––( Upper- and lower-limit alarm –––( Upper-limit alarm )––– Lower-limit alarm –()– Upper- and lower-limit range alarm 3––e Upper- and lower-limit alarms with standby sequence –––e Upper-limit alarm with standby sequence 3––– Lower-limit alarm with standby sequence 1––c Absolute-value alarm |
Similar Part No. - E5AX-PRR03 |
|
Similar Description - E5AX-PRR03 |
|
|
Link URL |
Privacy Policy |
ALLDATASHEET.COM |
Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Datasheet Upload | Contact us | Privacy Policy | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
Family Site : ic2ic.com |
icmetro.com |